FOUNDATION Fieldbus
FOUNDATION Fieldbus transmitters require a terminal voltage of 9.0V to 32.0V. See
page
170
for intrinsically safe and FISCO parameters.
Wiring Procedure
1.
2.
3.
4.
5.
6.
7.
Page 94
Ensure the loop power supply is off.
See
Figure 3-45
for parts locations. Loosen the end cap lock using a 1.5mm
Allen wrench.
Remove the end cap cover from the terminal block end of the Electronics
Housing.
Feed loop power leads through one end of the conduit entrances on either
side of the Electronics Housing. The Transmitter accepts up to 16AWG
wire.
Plug the unused conduit entrance with a conduit plug appropriate for the
environment.
Connect the positive loop and negative loop power
Transmitter is polarity insensitive.
Replace the end cap, and secure it in place.
SLG 700 SmartLine Level Transmitter User's Manual
terminals
. The
Revision 8