Honeywell SmartLine SLG 700 User Manual page 186

Level transmitter guided wave radar
Hide thumbs Also See for SmartLine SLG 700:
Table of Contents

Advertisement

Notes:
1. Non-Intrinsically Safe Operating Voltages:
Voltage at terminals = 14.0 to 42.0 Vdc (HART / 4-20mA)
2. Intrinsically Safe Entity Parameters
a.
Analog/ HART
Vmax= Ui = 30 V
b.
FOUNDATION Fieldbus-
Vmax= Ui = 30 V
c.
FOUNDATION Fieldbus (FISCO)- Entity Values
Vmax= Ui = 17.5 V
When Installed as FISCO Ta= -50C to 45C
For ic entity, refer to the control drawing 50098941
3. For ambient and process temperature ranges
Overfill Protection
SIL 2/3
Certification
China Pattern
Approval
Korean KC MSIP
Registration
Page 170
= 9.0 to 32.0 Vdc (FOUNDATION Fieldbus)
ia
Entity Values:
Imax= Ii= 225 mA
ia
Entity Values
Imax= Ii= 225 mA
Imax= Ii= 380 mA
and temperature classification
WHG
Certificate #: Z-65.16-556. TÜV-tested and approved for overfill protection
according to the German WHG regulations
IEC 61508 SIL 2 for non-redundant use and SIL 3 for redundant use
according to EXIDA and TÜV Nord Sys Tec GmbH & Co. KG under the
following standards: IEC61508-1: 2010; IEC 61508-2: 2010; IEC61508-3:
2010.
Note: Only transmitters with SIL markings are certified for SIL
applications. – Transmitters ordered with SIL certification will signify the
SIL Level on the SLG 700 Nameplate.
The SLG 700 is approved according to the Law on Metrology of the
People's Republic of China. China Pattern Approval identification numbers
2016-L262, 2016-L263, and 2016-L264.
SLG700 transmitters are registered under the clause 3, Article 58-2 of
Radio Waves Act. Registration # MSIP-REI-Ssi-SLG720
SLG 700 SmartLine Level Transmitter User's Manual
Ci = 4 nF
Li = 0
Ci = 0 nF
Li = 0
Ci = 0 nF
Li = 0
, see section
1.1
Pi =
W
1
Pi =1.
W
Pi =5.32 W
9.5
Revision 8