5.5 Replacing the Wire Probe

Overview
This instruction provides procedures for replacing wire probes for SLG700 SmartLine
Guided Wave Radar Transmitters.
Scope of this Kit Instruction
This kit instruction applies to the replacement of wire probes for all releases of the SLG700
SmartLine GWR Level Transmitter. However, R100 transmitters cannot be retrofitted with a
multi-twist wire probe without a hardware and firmware upgrade to a more recent version.
Applicability
All transmitters with a wire probe are supported. These can be identified with SW as the first
and second characters of the model Key.
For example: SLG72_-SW_ _ _ _ _ _ _ _ _ _ _-_ _ _ _-_-_ _ _.
Part Replacement Probes (reference)
This Kit Instruction applies to the following Parts Replacement Probes:
SLGP2_-_-SW_ _ _ _ _ _ _ _ _ _ _-_ _-_ _.
Required Publications
Publication #
Publication Title
SLG 700 SmartLine Guided Wave Radar User's Manual
34-SL-25-11
34-SL-25-06
SLG 700 SmartLine Level Transmitter Guided Wave Radar HART
User's Manual
34-SL-25-07
SLG 700 SmartLine Level Transmitter Guided Wave Radar FOUNDATION
Fieldbus Option Manual

Tools required

For this item
M5 set screw for wire probe end weight
(SWA, SWB)
Probe nut and swage (SLG720)
Probe nut and swage (SLG726)
Centering disk bolt (wire probe)
SLG720 wire swage
SLG726 wire swage
Page 142
SLG 700 SmartLine Level Transmitter User's Manual
Use this tool
AF 2.5 mm Allen key
AF 8 mm wrench (2 required)
AF 14 mm wrench (2 required)
AF 17 mm wrench
AF 7 mm wrench
AF 14 mm wrench
©