Page 2
In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The information and specifications in this document are subject to change without notice.
Page 3
Mounting, installation and wiring are covered in other documents. Honeywell does not recommend using devices for critical control where there is a single point of failure or where single points of failure result in unsafe conditions. OneWireless is targeted at open loop control, supervisory control, and controls that do not have environmental or safety consequences.
For more contact details for Europe, Asia, North and South Americas, please see back page. World Wide Web Honeywell Process Solutions Support Online: www.honeywellprocess.com/ Elsewhere Call your nearest Honeywell office. Training Classes Honeywell Automation College: http://www.automationcollege.com OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3 March 2012...
Page 5
Chassis Ground: Identifies a connection to the chassis or frame of the equipment shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements. continued Revision 3 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual March 2012...
Page 6
The ISA100 Wireless Compliant logo indicates the device has received ISA100.11a conformance certification and is registered with the Wireless Compliance Institute, assuring device interoperability. Canadian Registration Number OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3 March 2012...
1. Introduction 1.1. Purpose 1. Introduction Purpose This manual describes the Honeywell OneWireless XYR 6000 Pressure Transmitter function, operation and maintenance. Scope The manual includes: Details of topics that relate uniquely to the Honeywell XYR 6000 Pressure Transmitter, ...
Lithuania Cyprus Malta Czech Republic Netherlands Denmark Norway Estonia Poland Finland Portugal France Romania Germany Slovakia Greece Slovenia Hungary Spain Iceland Sweden Ireland Switzerland Italy United Kingdom Revision 3 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual March 2012...
Page 17
IEC 61241-0 : 1999 IEC 61241-1 : 1999 *See individual Product manuals as defined in References for exact Models ** At time of Printing Certification was pending. Revision 3 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual March 2012...
Special precautions shall be taken to prevent the surface of the antenna of the XYR 6000 Wireless Transmitter from being electrostatically charged. OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3 March 2012...
Agency compliance information This section contains the Federal Communications Commission (FCC), Industry Canada (IC) and Radio Frequency compliance statements for the OneWireless XYR 6000 Wireless Transmitters device. ATTENTION XYR 6000 units must be professionally installed in accordance with the requirements specified in the OneWireless XYR 6000 Agency Compliance Professional Installation Guide.
Installations in France must limit EIRP to 10dBm, for operating modes utilizing frequencies in the range of 2,454 – 2,483.5MHz. Japanese Restrictions For locations in Japan the transmitter power is restricted to 12.14dBm/Mhz {(32mW (15.4 dBm)] maximum EIRP including the antenna. OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3 March 2012...
Setting user trim points will effectively override the calibration zero. Normally the calibration zero is only required if you do not intend to provide process- specific trim points. Revision 3 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual March 2012...
0-5 to 0-100 psi/0-0.34 to 0-7 bar Compound Characterized Honeywell XYR6000 pressure transmitters are fully characterized at the factory and have an applied factory calibration over the range of the transmitter (URL). Field calibration is provided to allow up to 5% adjustment over a reduced operating range providing accuracy within .075% of the reduce range or ±0.025...
Page 23
If the calibration status does not return SUCCESS stop and call Honeywell customer support for further assistance. Cal Clear will clear any previous user calibration including and zero bias established using a CAL ZERO command.
Page 24
5% of the URL. OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3...
AITB and device blocks contain standard parameters common to all ISA100.11a-compliant transmitters as well as model-specific parameters. The radio block contains parameters for communication with the wireless network. Revision 3 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual March 2012...
WFN ID by accessing the quick view mode using the Provisioning Device navigation keys. For more information on parameters, refer to the following documents. OneWireless User’s Guide OneWireless Parameter Reference OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3 March 2012...
Transmitter has validated the key and has No action required. made a secure connection with at least two Multinodes. Transmitter should appear in OneWireless User Inteface as an uncommissioned device. OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3 March 2012...
Atmosphere Pounds per square inch PSIA Pounds per square inch absolute PSIG Pounds per square inch gage GCM2 grams per centimeter square KGCM2 Kilograms per centimeter square Revision 3 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual March 2012...
Description CMPS cubic meters per second CMPM cubic meters per minute CMPH cubic meters per hour CMPD cubic meters per day liters per second liters per minute OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3 March 2012...
Page 31
4. Perform Cal Low and Cal high in pressure units only if required. Calibration is optional and is done only if the factory or default calibration is not sufficient. Revision 3 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual March 2012...
38. invalid. OVR TEMP Over Temperature The meter body has Determine cause excessive exceeded the maximum temperature. temperature as defined by the meter body characterization data. OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3 March 2012...
Page 33
RAM Fault* Startup diagnostics Replace sensor module. See page detected defect in Processor Random Access Memory The following statuses are displayed only in OneWireless UI Device Status. Revision 3 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual March 2012...
Page 34
Watchdog Timer Error* Sensor Watchdog Clear by warm restart of device. If Timeout. The processor condition persists contact was restarted due to Honeywell service. unexpected operation. OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3 March 2012...
Sensor device revision SBLD Sensor build number Radio Type DSSS RBLD Radio build number Wireless field network identifier Network device address MODE/CHANNEL Frequency hopping mode & channel Revision 3 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual March 2012...
Secondary receive signal strength. Same as PRI RSSI. Read only. WFN ID Wireless Field Network ID. Read only. DEV ADD Device address. Read only. TX POWER Radio transmit power. Read only. OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3 March 2012...
Main menu The main menu is shown below. Details start on the next page. Figure 5-1 Main menu Revision 3 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual March 2012...
Provisioning Device, clear the transmitter’s key and reset its configuration to factory defaults (such as for deprovisioning). Figure 5-2 Security and Node Deployment OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3 March 2012...
Page 39
Wireless System Gateway user interface and getting more. For more details on keys, refer to Getting Started with Honeywell OneWireless Solutions. Revision 3 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual...
Go to the upper menu level. When changing a number value, move cursor to the left/more significant digit, then wrap around to the least significant digit. OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3 March 2012...
Do not confuse this with the other nameplate item marked “Serial.” Network ID Network Address of the device in hexadecimal. IP Address: IP Address of radio Revision 3 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual March 2012...
Page 42
Joining – The device is negotiating the parameters of the wireless connection. Joined – A secure connection is formed with the network. The second line contains detailed state information useful for problem reporting. OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3 March 2012...
Reads the transmission power level of the transmitter radio. Read Tag Name Reads the transmitter’s tag name Write Tag Name Write the transmitter’s tag name with the entered text, maximum 16 characters OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3 March 2012...
For example, if applying 68 N-M (50 Lb-Ft), select a torque wrench with range of 7 N-M to 136 N-M (5 to 100 Lb-Ft). Revision 3 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual March 2012...
Use a torque wrench to gradually tighten nuts to torque rating shown in Table 6-2, in sequence shown in Figure 6-1. Tighten head bolts in stages of 1/3 full torque, 2/3 full torque, and then full torque. Return transmitter to service. OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3 March 2012...
Table 6-3 Sensor module replacement Step Action Honeywell recommends that the transmitter be removed from service and moved to a clean area before servicing. Loosen the M3 locking set screw on the display end-cap. See item 1 in Figure 6-2. Unscrew and remove the end cap.
Batteries must not be changed in an explosive gas atmosphere. If IS Battery Pack, Honeywell 50047517-001, has been installed in the Wireless Transmitter, the transmitter enclosure maybe opened when an explosive gas atmosphere is present. Otherwise, do not open transmitter enclosure when and explosive gas atmosphere is present.
0.4 to 0.6 N-M (3.5 – 5.3 Lb-in). Reconnect the Battery Pack connector Honeywell recommends lubricating the end cap thread with a silicone grease such as Dow Corning #55 or equivalent before replacing the end cap Screw the cap back on and tighten the M3 locking screw Revision 3 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual...
Disconnect all power from transmitter input sources before accessing the 24V power module. Failure to do so could result in death or serious injury if the input terminals or wires are accidentally touched. OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3 March 2012...
0,4 – 0,6 N-M (3.5 – 5.3 Lb-in). Re-connect battery connector. Honeywell recommends lubricating the end cap O-ring with a Silicone Grease such as Dow Corning #55 or equivalent before replacing the end cap. Screw the end cap back on and tighten the M3 locking screw.
If electrostatically charged, discharge of the antenna shroud to a person or a tool could possibly ignite a surrounding hazardous atmosphere. Revision 3 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual March 2012...
See items 2 in Figure 6-6. Torque screws to 0,4 – 0,6 N-M (3.5 – 5.3 Lb- in). Replace the front end cap. Honeywell recommends lubricating the front end cap O-ring with a Silicone Grease such as Dow Corning #55 or equivalent before replacing the end cap.
6. Maintenance/Repair 6.8. Parts Meter body Use the following figures and table to find replacement parts. Figure 6-7 STDW1xx, STDW9xx Figure 6-8 STGW944, STGW974 Revision 3 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual March 2012...
Page 62
NOTE 2: The Kit for Process Heads without side vent/drain does not include Pipe Plugs (K1). Reference Head: 51452951-001 Carbon Steel Blind Reference Head 51452951-002 316 SS Blind Reference Head (Model Selection Guide HR Option) OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3 March 2012...
Meter body nameplate 30757503-001 Electronics enclosure seals kit for LGP/LAP models. Kit includes: ……..…….…………… O-ring for transmitter end caps ………………………… O-ring, meter body to electronics housing Revision 3 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual March 2012...
Dimension drawings Dimension drawings are available for each transmitter model. If you need a copy of a drawing, please determine the appropriate drawing number from the following tables and contact your Honeywell representative. Table 6-7 Drawing numbers for DP models STDW1xx, STDW9xx Angle Bracket (“MB”...
1143 ‐ psig pounds per square inch gauge 1144 ‐ g/cm² gram per square centimeter 1145 ‐ kg/cm² kilogram per square centimeter 1147 ‐ inH2O (4°C) inches of water at 4°C 1148 ‐ inH2O (68°F) inches of water at 68°F 1150 ‐ mmH2O (4°C) millimeters of water at 4°C 1151 ‐ mmH2O (68°F) millimeters of water at 68°F 1156 ‐ inHg (0°C) inches of mercury at 0°C 1158 ‐ mmHg (0°C) millimeters of mercury at 0°C 1342 ‐ % percent SCALE.DECIMAL Channel decimal points. Uint8 1 Read/Write Static Revision 3 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual March 2012...
Page 66
1137 ‐ bar 1138 ‐ mbar millibar 1141 ‐ psi pounds per square inch 1142 ‐ psia pounds per square inch absolute 1143 ‐ psig pounds per square inch gauge 1144 ‐ g/cm² gram per square centimeter 1145 ‐ kg/cm² kilogram per square centimeter 1147 ‐ inH2O (4°C) inches of water at 4°C 1148 ‐ inH2O (68°F) inches of water at 68°F 1150 ‐ mmH2O (4°C) millimeters of water at 4°C 1151 ‐ mmH2O (68°F) millimeters of water at 68°F 1156 ‐ inHg (0°C) inches of mercury at 0°C 1158 ‐ mmHg (0°C) millimeters of mercury at 0°C 1342 ‐ % percent OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3 March 2012...
Page 67
1158 ‐ mmHg (0°C) millimeters of mercury at 0°C 1342 ‐ % percent The number of digits to the right of the decimal point which should be used by an interface device in displaying the specified SENSOR_RANGE.DECIMAL parameter. Uint8 1 Read Only Constant Maximum static pressure rating in selected MAX_SP scale units Float 4 Read Only Constant Maximum over pressure rating in selected scale units Float MAX_OVP 4 Read Only Constant Revision 3 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual March 2012...
256 ‐ No Radio Error Radio is not present or not functioning 4096 ‐ Low External Power External power is low 65536 ‐ Program Memory Fault Program memory is corrupted 131072 ‐ RAM Fault Random access memory is corrupted 262144 ‐ NVM Fault Non‐volatile memory is corrupted 524288 ‐ ADC Failure Analog to digital converter failed 1048576 ‐ Characterization Memory Fault Characterization memory fault 16777216 ‐ Meter Body Over Temperature Meter body temperature is too high Pressure input exceeds twice the upper 33554432 ‐ Meter Body Overload range limit 67108864 ‐ Excess Zero Calibration Zero calibration exeeds 5 percent 134217728 ‐ Excess Span Calibration Span calibration exeeds 5 percent 268435456 ‐ Excess Calibrated Range Calibrated span exceeds the sensor span 536870912 ‐ Calibration Cleared Calibration was reset OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3 March 2012...
Page 69
2 Read Only Static JOIN_ATTEMPT_COUNT Field device radio network join attempt counter. Uint16 2 Read Only Static RESET_COUNTERS Field device radio reset counters command. Boolean 1 Read/Write Static ROUTING_ASSIGNMENT Field device radio network routing assignment. Uint8 1 Read/Write Static 0 ‐ Routing Disabled Routing Disabled 1 ‐ Routing Enabled Routing Enabled 2 ‐ Not Applicable Not Applicable Revision 3 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual March 2012...
Page 70
Dynamic Read response timeouts between WDM and field STAT_READRSPTIMEOUT device application. Uint32 4 Read Only Dynamic STAT_WRITEREQSEND Write request from WDM to field device application. Uint32 4 Read Only Dynamic STAT_WRITEREQRECV Write requests from field device application to WDM. Uint32 4 Read Only Dynamic Write request timeouts between WDM and field STAT_WRITEREQTIMEOUT device application. Uint32 4 Read Only Dynamic OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual Revision 3 March 2012...
Page 71
64 Read Only Dynamic STAT_RADIOVENDOR Field device radio vendor string. VisibleString 24 Read Only Dynamic STAT_RADIOMODEL Field device radio model string. VisibleString 16 Read Only Dynamic STAT_RADIOREVISION Field device radio revision string. VisibleString 16 Read Only Dynamic Field device serial number. STAT_SERIALNUMBER VisibleString 16 Read Only Dynamic Revision 3 OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual March 2012...
Page 72
ASIA PACIFIC EMEA NORTH AMERICA SOUTH AMERICA (TAC) Honeywell Process Solutions, Honeywell Process Solutions, Honeywell do Brasil & Cia hfs-tac- Phone: + 80012026455 or +44 Phone: 1-800-423-9883 Phone: +(55-11) 7266-1900 support@honeywell.com (0)1202645583 Or 1-800-343-0228 FAX: +(55-11) 7266-1905...