Changing Block Modes; Configure/Setup Parameters; Transducer Block Parameters - Siemens SITRANS LR560 Operating Instructions Manual

Foundation fieldbus radar level transmitter
Hide thumbs Also See for SITRANS LR560:
Table of Contents

Advertisement

Changing Block Modes

Note: Resource Block overrides Level Transducer Block. Changing Resource Block
mode will also change Level Transducer Block mode.
To change any block mode follow the same procedure as for changing Resource Block
mode.
To change Resource Block mode
1)
Navigate to Configure/Setup > Resource Block > Operation > Block Mode and click
Block Mode to open the dialog window.
2)
Select the desired Target mode and deselect the other option. Click Apply (the Apply
button is activated when a change is made).
3)
Return to the main menu.

Configure/Setup Parameters

Transducer Block Parameters

Identification and Operation are common to all three Transducer Blocks: Level
Transducer Block, LCD Transducer Block, and Diagnostic Transducer Block.
Identification (LTB, LCD, DIAG)
Navigate to Configure/Setup > LTB and click Identification to open the dialog window for
access to:
Identification:
TAG
Read only. Description for the associated block: device tag prefixed by block
type.
7ML19985LY01
SITRANS LR560 (FF) – INSTRUCTION MANUAL
Target Mode deselected
Target Mode selected
Apply
Page 49