General Fault Codes - Siemens SITRANS LR560 Operating Instructions Manual

Foundation fieldbus radar level transmitter
Hide thumbs Also See for SITRANS LR560:
Table of Contents

Advertisement

Priority
Icon
Level
2
3

General Fault Codes

Notes:
If more than one fault is present, the device status indicator and text for each fault
alternate at 2 second intervals.
Code
Meaning
/Icon
S: 0
The device was unable to get a mea-
surement within the LOE Timer period.
Possible causes: faulty installation,
antenna material buildup, foaming/
other adverse process conditions,
invalid calibration range.
S: 2
Unable to collect profile because of a
power condition that is outside the
operating range of the device.
Page 130
SITRANS LR560 (FF)– INSTRUCTION MANUAL
Meaning (cont' d )
• Simulation or substitute value
• Communication is good; device is in simulation mode or works with
substitute values.
• Out of operation
• Communication is good; device is out of action.
• No data exchange
• Write access enabled
• Write access disabled
General Fault Codes
Corrective Action
• Ensure installation details are cor-
rect.
• Ensure no material buildup. Clean if
necessary.
• Adjust process conditions to mini-
mize foam or other adverse condi-
tions.
• Correct range calibration.
• If fault persists, contact your local
Siemens representative.
Repair required. Contact your local
Siemens representative.
7ML19985LY01

Advertisement

Table of Contents
loading