Siemens SITRANS LR560 Operating Instructions Manual page 53

Foundation fieldbus radar level transmitter
Hide thumbs Also See for SITRANS LR560:
Table of Contents

Advertisement

Step 1 – Identification
Click Step 1 - Identification.
If you wish to accept the default values, go directly to Step 2 (Descriptor, Message, and
Date fields can be left blank). Or if desired, make changes then click Apply.
Step 2 – Application
Notes:
• Selecting either STEEL or CONCRETE does a functional reset (see Master Reset (4.1.)
on page 110).
• Selecting STEEL changes the setting for Position Detect (2.7.3.3.) to Rising Edge. and
for Algorithm (2.7.3.1.) to F.
• Selecting CONCRETE changes the setting for Position Detect (2.7.3.3.) to Rising Edge
and for Algorithm (2.7.3.1.) to ALF.
Click Step 2 - Application. If you wish to accept the default values, go directly to Step 3.
Or select a different vessel type (steel or concrete). [This changes the setting for Position
Detect (2.4.5.2.) to Rising Edge.] Then click Apply.
7ML19985LY01
SITRANS LR560 (FF) – INSTRUCTION MANUAL
Page 47