2.4.3. Minimum Sensor Value
Read only. Defines the minimum usable value for the measuring range, in units
defined in Unit (2.3.1.).
(Default = 0.0 m)
For access via AMS Device Manager see Range under Signal Processing (LTB)
on page 53
2.4.4. Maximum Sensor Value
Read only. Defines the maximum usable value for the measuring range, in units
defined in Unit (2.3.1.).
Default depends on device:
For access via AMS Device Manager see Range under Signal Processing (LTB)
on page 53
2.4.5. Echo Select
2.4.5.1.
Selects the algorithm to be applied to the echo profile to extract the true
echo.
Options
7ML19985LY01
sensor reference point (flange face)
sensor value (distance from sensor reference point
Level
.
40 m device default
100 m device default
.
Algorithm
ALF
A
L
*
F
AL
AF
LF
BLF
BL
BF
TF
SITRANS LR560 (FF) – INSTRUCTION MANUAL
to the target)
=
45.0 m
=
105 m)
Area Largest First
Echo Area
Largest Echo
First Echo
Area Largest
Area First
Largest First
Best of First or Largest echo
Best Largest
Best First
LAST
True First
Page 95