Siemens SITRANS LR560 Operating Instructions Manual page 137

Foundation fieldbus radar level transmitter
Hide thumbs Also See for SITRANS LR560:
Table of Contents

Advertisement

Code
Meaning
/Icon
S: 3
Device is nearing its lifetime limit as
defined in Remaining Lifetime (4.2.3.)
and has triggered Reminder 1
(Required) (4.2.5.).
S: 4
Device is nearing its lifetime limit as
defined in Remaining Lifetime (4.2.3.)
and has triggered Reminder 2
(Demanded) (4.2.6.).
S: 6
Sensor is nearing its lifetime limit as
defined in Remaining Lifetime (4.3.3.)
and has triggered Reminder 1
(Required) (4.3.5.).
S: 7
Sensor is nearing its lifetime limit as
defined in
has triggered a Maintenance
Demanded reminder
S: 8
Service interval as defined in
expired and has triggered a Mainte-
nance Required reminder
S: 9
Service interval as defined in
expired and has triggered a Mainte-
nance Demanded reminder
Input parameters Low Calibration Point
S: 10
(2.3.5.1.) and High Calibration Point
(2.3.5.2.) are the same.
S: 11
Internal temperature sensor failure.
7ML19985LY01
General Fault Codes (cont'd)
4.3.3.Remaining Lifetime
(4.3.6.)
.
4.4. 1 .
(4.4.5.)
4.4. 1 .
(4.4.6.)
SITRANS LR560 (FF) – INSTRUCTION MANUAL
Corrective Action
Replacement is recommended.
Replacement is recommended.
Replacement is recommended.
Replacement is recommended.
and
has
Perform service.
.
has
Perform service.
.
• Check calibration settings of
device.
• Ensure settings for High Calibration
Point and Low Calibration Point are
different.
Repair required: contact your local
Siemens representative.
Page 131