2.3.5.4.
The level when the material is at Low Calibration Point. The unit is defined
in Level Unit (2.3.2.).
Values
2.3.5.5.
The level when the material is at High Calibration Point. The unit is defined
in Level Unit (2.3.2.).
Values
2.3.5.6.
A constant offset that can be added to Level. The unit is defined in Level
Unit (2.3.2.).
Values
2.3.6. Rate
2.3.6.1.
Sets the reaction speed of the device to measurement changes.
Notes:
• Changing Response Rate resets Fill Rate/Min (2.3.6.2.), and Empty
• Selecting SLOW Response Rate changes setting for
Response Rate
(2.3.6.1.)
Use a setting just faster than the maximum filling or emptying rate
(whichever is faster).
Page 92
SITRANS LR560 (FF) – INSTRUCTION MANUAL
Low Level Point
Range: -999999 to 999999
Default: 0%
High Level Point
Range: -999999 to 999999
Default: 100%
Level Offset
Range: -999999 to 999999
Default: 0%
Response Rate
rate/Min (2.3.6.3.).
(2.8.3.)
to 0.9.
slow
*
medium
fast
Fill Rate/Min (2.3.6.2.)/
Empty rate/Min (2.3.6.3.)
0.1 m/min (0.32 ft/min)
1.0 m/min (3.28 ft/min)
10.0 m/min (32.8 ft/min)
Average amount