Information List; Setting Groups - Siemens SIPROTEC 7UT613 series Manual

Differential protection
Hide thumbs Also See for SIPROTEC 7UT613 series:
Table of Contents

Advertisement

2 Functions
Addr.
Parameter
836
SwitchgCBaux M1
837
SwitchgCBaux M2
838
SwitchgCBaux M3
839
SwitchgCBaux M4
840
SwitchgCBaux M5
841
SwitchgCBaux E1
851A
TMin TRIP CMD
2.1.4.6

Information List

No.
Information
5145
>Reverse Rot.
5147
Rotation L1L2L3
5148
Rotation L1L3L2
2.1.5

Setting Groups

2.1.5.1
Setting Groups
Purpose of Setting
Groups
96
Setting Options
(Setting options depend
on configuration)
(Setting options depend
on configuration)
(Setting options depend
on configuration)
(Setting options depend
on configuration)
(Setting options depend
on configuration)
(Setting options depend
on configuration)
0.01 .. 32.00 sec
Type of In-
formation
SP
OUT
OUT
Four independent groups of parameters can be set for the device functions. During op-
eration, you may switch between setting groups locally, via binary inputs (if so config-
ured), via the operator or service interface using a personal computer, or via the
system interface.
A setting group includes the setting values for all functions that have been selected as
Enabled during configuration of the functional scope. In the 7UT613/63x device, four
independent setting groups (Group A to Group D) are available. Whereas setting
values and options may vary, the selected scope of functions is the same for all
groups.
Setting groups enable the user to save the corresponding settings for each applica-
tion. Settings may be loaded quickly. While all setting groups are stored in the relay,
only one setting group may be active at a given time. If multiple setting groups are not
required, Group Group A is the default selection.
If the changeover option is desired, group changeover must be set to Grp Chge
OPTION = Enabled during configuration of the functional scope (address 103). For
the setting of the function parameters, each of the required 4 setting groups Group A
to Group D must be configured.
Default Setting
None
Switchgear / CBaux at Measuring
Loc. M1
None
Switchgear / CBaux at Measuring
Loc. M2
None
Switchgear / CBaux at Measuring
Loc. M3
None
Switchgear / CBaux at Measuring
Loc. M4
None
Switchgear / CBaux at Measuring
Loc. M5
None
Switchgear / CBaux at ext. location
1
0.15 sec
Minimum TRIP Command Duration
Comments
>Reverse Phase Rotation
Phase Rotation L1L2L3
Phase Rotation L1L3L2
Comments
7UT613/63x Manual
C53000-G1176-C160-2