4.3
Restricted earth fault protection
Setting Ranges
Operating Time
Frequency Influence
7UT613/63x Manual
C53000-G1176-C160-2
Differential current
Limit angle
Trip characteristic
Pickup tolerance
(with preset characteristic parameters and one
3-phase measuring location)
Time delay
Time tolerance
The set times are pure delay times
Pickup time at frequency
at 1.5 · set value I
> approx. high-speed relays
REF
> approx. high-speed relays
at 2.5 · set value I
REF
Dropout time, approx.
Dropout ratio
Frequency influence
Figure 4-6
Tripping characteristic of the restricted earth fault protection depending on the
earth current ratio 3I
I
> = setting; I
REF
4.3 Restricted earth fault protection
I
>/I
0.05 to 2.00
REF
NObj
ϕ
110° (fixed)
REF
see Figure 4-6
5 % at I < 5 · I
T
0.00 s to 60.00 s
REF
or ∞ (no trip)
1 % of set value or 10 ms
high-speed relays
high-speed relays
within the frequency tagging range
"/3I
' (both currents in phase + or counter-phase —);
0
0
= tripping current
Trip
Steps 0.01
N
Steps 0.01 s
50 Hz
60 Hz
16.7 Hz
35 ms
30 ms
110 ms
30 ms
25 ms
105 ms
33 ms
29 ms
87 ms
28 ms
24 ms
82 ms
26 ms
23 ms
51 ms
approx. 0.7
441