Setting Notes; Settings - Siemens SIPROTEC 7UT613 series Manual

Differential protection
Hide thumbs Also See for SIPROTEC 7UT613 series:
Table of Contents

Advertisement

Blocking Signal for
External Faults
Figure 2-113
CFC chart for blocking of a pressure sensor during external fault

2.18.2 Setting Notes

General

2.18.3 Settings

Addr.
Parameter
8601
EXTERN TRIP 1
8602
T DELAY
8701
EXTERN TRIP 2
8702
T DELAY
7UT613/63x Manual
C53000-G1176-C160-2
For transformers so-called sudden pressure relays (SPR) are occasionally installed in
the tank which are meant to switch off the transformer in case of a sudden pressure
increase. Not only transformer failures but also high traversing fault currents originat-
ing from external faults can lead to a pressure increase.
External faults are quickly recognised by the 7UT613/63x (also refer to differential pro-
tection, „Add-on Restraint during External Faults", section 2.2). A blocking signal can
be created by means of a CFC logic in order to prevent from erroneous trip of the SPR.
The direct external trip functions are only enabled if addresses 186 EXT. TRIP 1
and/or 187 EXT. TRIP 2 have been set to Enabled during the configuration of the
functional scope.
Addresses 8601 EXTERN TRIP 1 and 8701 EXTERN TRIP 2 are used to switch the
functions individually ON or OFF, or to block only the trip command (Block relay).
Signals included from outside can be stabilised by means of a delay time and thus in-
crease the dynamic margin against interference signals. For external trip functions 1
settings are done in address 8602 T DELAY, for external trip function 2 in address
8702 T DELAY
Setting Options
OFF
ON
Block relay
0.00 .. 60.00 sec; ∞
OFF
ON
Block relay
0.00 .. 60.00 sec; ∞
2.18 External Trip Commands
Default Setting
OFF
External Trip Function 1
1.00 sec
Ext. Trip 1 Time Delay
OFF
External Trip Function 2
1.00 sec
Ext. Trip 2 Time Delay
Comments