Siemens SIPROTEC 7UT613 series Manual page 235

Differential protection
Hide thumbs Also See for SIPROTEC 7UT613 series:
Table of Contents

Advertisement

Addr.
Parameter
9063
RTD 6 STAGE 1
9064
RTD 6 STAGE 1
9065
RTD 6 STAGE 2
9066
RTD 6 STAGE 2
9071A
RTD 7 TYPE
9072A
RTD 7 LOCATION
9073
RTD 7 STAGE 1
9074
RTD 7 STAGE 1
9075
RTD 7 STAGE 2
9076
RTD 7 STAGE 2
9081A
RTD 8 TYPE
9082A
RTD 8 LOCATION
9083
RTD 8 STAGE 1
9084
RTD 8 STAGE 1
9085
RTD 8 STAGE 2
9086
RTD 8 STAGE 2
9091A
RTD 9 TYPE
7UT613/63x Manual
C53000-G1176-C160-2
Setting Options
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
2.10 RTD-Boxes for Overload Detection
Default Setting
100 °C
RTD 6: Temperature Stage 1
Pickup
212 °F
RTD 6: Temperature Stage 1
Pickup
120 °C
RTD 6: Temperature Stage 2
Pickup
248 °F
RTD 6: Temperature Stage 2
Pickup
Not connected
RTD 7: Type
Other
RTD 7: Location
100 °C
RTD 7: Temperature Stage 1
Pickup
212 °F
RTD 7: Temperature Stage 1
Pickup
120 °C
RTD 7: Temperature Stage 2
Pickup
248 °F
RTD 7: Temperature Stage 2
Pickup
Not connected
RTD 8: Type
Other
RTD 8: Location
100 °C
RTD 8: Temperature Stage 1
Pickup
212 °F
RTD 8: Temperature Stage 1
Pickup
120 °C
RTD 8: Temperature Stage 2
Pickup
248 °F
RTD 8: Temperature Stage 2
Pickup
Not connected
RTD 9: Type
Comments
235

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents