Siemens SIPROTEC 7UT613 series Manual page 431

Differential protection
Hide thumbs Also See for SIPROTEC 7UT613 series:
Table of Contents

Advertisement

EMC Tests for the Interference Emission (type test)
7UT613/63x Manual
C53000-G1176-C160-2
Irradiation with HF field, frequency sweep
IEC 60255-22-3; Class III
IEC 61000-4-3, Class III
Irradiation with HF field, single frequencies
IEC 60255-22-3;
IEC 61000-4-3
– amplitude modulated
– pulse modulated
Fast transient disturbance/burst
IEC 60255-22-4 and
IEC 61000-4-4, Class IV
High energy surge voltages (SURGE),
IEC 61000-4-5 Installation Class 3
—auxiliary voltage
Measuring inputs, binary inputs and relay out-
puts
Line conducted HF, amplitude modulated
IEC 61000-4-6, Class III
Power system frequency magnetic field
IEC 61000-4-8, Class IV
IEC 60255-6
Oscillatory surge withstand capability
IEEE Std C37.90.1
Fast transient surge withstand cap.
IEEE Std C37.90.1
Damped oscillations
IEC 60694, IEC 61000-4-12
Standard:
Conducted interference, only power supply
voltage
IEC-CISPR 22
Radio interference field strength
IEC-CISPR 22
Harmonic currents on the network lead at 230
V AC
IEC 61000-3-2
Voltage fluctuations and flicker on the network
lead at 230 VAC
IEC 61000-3-3
10 V/m; 80 MHz to 1000 MHz;
10 V/m; 800 MHz to 960 MHz;
20 V/m; 1.4 GHz to 2.0 GHz;
80 % AM; 1 kHz
Class III: 10 V/m
80/160/450/900 MHz; 80 % AM; duty cycle
>10 s
900 MHz; 50 % PM, repetition frequency
200 Hz
4 kV; 5/50 ns; 5 kHz; burst length = 15 ms;
repetition rate 300 ms; both polarities;
= 50 Ω; test duration 1 min
R
i
impulse: 1.2/50 µ
common mode: 2 kV; 12 Ω; 9 µF
Diff. mode:1 kV; 2 Ω; 18 µF
common mode: 2 kV; 42Ω; 0. 5 µF
diff. mode: 1 kV; 42Ω; 0. 5 µF
10 V; 150 kHz to 80 MHz: 80 % AM; 1 kHz
30 A/m continuous; 300 A/m for 3 s; 50 Hz
0.5 mT; 50 Hz
2.5 kV (peak value); 1 MHz; τ = 15 µs;
400 pulses per s; test duration 2 s; R
4 kV; 5/50 ns; 5 kHz; burst length = 15 ms;
Repetition rate 300 ms; both polarities;
= 50 Ω; test duration 1 min
R
i
2.5 kV (peak value), polarity alternating
100 kHz, 1 MHz, 10 MHz and 50 MHz;
= 200 Ω
R
i
EN 61000-* (generic standard)
150 kHz to 30 MH
limit class B
30 MHz to 1000 MHz
Limit class B
Class A limits are observed
Limits are observed
4.1 General
= 200 Ω
i
431

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents