Information List - Siemens SIPROTEC 7UT613 series Manual

Differential protection
Hide thumbs Also See for SIPROTEC 7UT613 series:
Table of Contents

Advertisement

Addr.
Parameter
4024
D I2p
4025
I2p DROP-OUT
4026
IEC CURVE
4027
ANSI CURVE
4031
I2>
4032
I2 tolerance
4033
T WARN
4034
FACTOR K
4035
T COOL DOWN
2.8.4

Information List

No.
Information
5143
>BLOCK I2
5146
>RM th.rep. I2
5151
I2 OFF
5152
I2 BLOCKED
5153
I2 ACTIVE
5157
I2 th. Warn
5158
RM th.rep. I2
5159
I2>> picked up
5160
I2>> TRIP
I2 Θ TRIP
5161
5165
I2> picked up
5166
I2p picked up
5167
I2th Pick-up
5168
I2 Adap.fact.
5170
I2 TRIP
5172
I2 Not avail.
5178
I2> TRIP
5179
I2p TRIP
7UT613/63x Manual
C53000-G1176-C160-2
C
Setting Options
0.50 .. 15.00 ; ∞
Instantaneous
Disk Emulation
Normal Inverse
Very Inverse
Extremely Inv.
Extremely Inv.
Inverse
Moderately Inv.
Very Inverse
0.01 .. 8.00 A; ∞
1A
0.05 .. 40.00 A; ∞
5A
0.01 .. 0.80 I/InS; ∞
0.00 .. 60.00 sec; ∞
1.0 .. 100.0 sec; ∞
0 .. 50000 sec
Type of In-
formation
SP
>BLOCK I2 (Unbalance Load)
SP
>Reset memory for thermal replica I2
OUT
I2 switched OFF
OUT
I2 is BLOCKED
OUT
I2 is ACTIVE
OUT
Unbalanced load: Thermal warning stage
OUT
Reset memory of thermal replica I2
OUT
I2>> picked up
OUT
Unbalanced load: TRIP of current stage
OUT
Unbalanced load: TRIP of thermal stage
OUT
I2> picked up
OUT
I2p picked up
OUT
Unbalanced load: Pick-up I2 thermal
OUT
I2 err.: adverse Adaption factor CT
OUT
I2 TRIP
OUT
I2 err.: Not available for this object
OUT
I2> TRIP
OUT
I2p TRIP
2.8 Unbalanced Load Protection
Default Setting
5.00
D I2p Time Dial
Instantaneous
I2p Drop-out Characteris-
tic
Extremely Inv.
IEC Curve
Extremely Inv.
ANSI Curve
0.10 A
Continously Permissible
Current I2
0.50 A
0.16 I/InS
Permissable quiescent un-
balanced load
20.00 sec
Warning Stage Time
Delay
18.7 sec
Negativ Sequence Factor
K
1650 sec
Time for Cooling Down
Comments
Comments
219