2.10.3 Settings

Addr.
Parameter
9011A
RTD 1 TYPE
9012A
RTD 1 LOCATION
9013
RTD 1 STAGE 1
9014
RTD 1 STAGE 1
9015
RTD 1 STAGE 2
9016
RTD 1 STAGE 2
9021A
RTD 2 TYPE
9022A
RTD 2 LOCATION
9023
RTD 2 STAGE 1
9024
RTD 2 STAGE 1
9025
RTD 2 STAGE 2
9026
RTD 2 STAGE 2
9031A
RTD 3 TYPE
9032A
RTD 3 LOCATION
9033
RTD 3 STAGE 1
7UT613/63x Manual
C53000-G1176-C160-2
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
Setting Options
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
2.10 RTD-Boxes for Overload Detection
Default Setting
Pt 100 Ω
RTD 1: Type
Oil
RTD 1: Location
100 °C
RTD 1: Temperature Stage 1
Pickup
212 °F
RTD 1: Temperature Stage 1
Pickup
120 °C
RTD 1: Temperature Stage 2
Pickup
248 °F
RTD 1: Temperature Stage 2
Pickup
Not connected
RTD 2: Type
Other
RTD 2: Location
100 °C
RTD 2: Temperature Stage 1
Pickup
212 °F
RTD 2: Temperature Stage 1
Pickup
120 °C
RTD 2: Temperature Stage 2
Pickup
248 °F
RTD 2: Temperature Stage 2
Pickup
Not connected
RTD 3: Type
Other
RTD 3: Location
100 °C
RTD 3: Temperature Stage 1
Pickup