Siemens SIPROTEC 7UT613 series Manual page 562

Differential protection
Hide thumbs Also See for SIPROTEC 7UT613 series:
Table of Contents

Advertisement

A Appendix
Addr.
Parameter
723
IN-SEC CT IX2
731
EARTH IX3 AT
732
IN-PRI CT IX3
733
IN-SEC CT IX3
734
FACTOR CT IX3
741
EARTH IX4 AT
742
IN-PRI CT IX4
743
IN-SEC CT IX4
744
FACTOR CT IX4
801
UN-PRI VT SET
802
UN-SEC VT SET
803
CORRECT. U Ang
811
UN-PRI VT U4
812
UN-SEC VT U4
816
Uph / Udelta
817
Uph(U4)/Udelta
831
SwitchgCBaux S1
832
SwitchgCBaux S2
833
SwitchgCBaux S3
834
SwitchgCBaux S4
835
SwitchgCBaux S5
836
SwitchgCBaux M1
837
SwitchgCBaux M2
838
SwitchgCBaux M3
839
SwitchgCBaux M4
840
SwitchgCBaux M5
841
SwitchgCBaux E1
851A
TMin TRIP CMD
901
WAVEFORMTRIGGER
903
MAX. LENGTH
904
PRE. TRIG. TIME
905
POST REC. TIME
906
BinIn CAPT.TIME
1107
P,Q sign
562
Function
C
P.System Data 1
1A
5A
P.System Data 1
Terminal R7
Terminal R8
P.System Data 1
1 .. 100000 A
P.System Data 1
1A
5A
P.System Data 1
1.0 .. 300.0
P.System Data 1
Terminal P7
Terminal P8
P.System Data 1
1 .. 100000 A
P.System Data 1
1A
5A
P.System Data 1
1.0 .. 300.0
P.System Data 1
1.0 .. 1200.0 kV
P.System Data 1
80 .. 125 V
-5.00 .. 5.00 °
P.System Data 1
P.System Data 1
1.0 .. 1200.0 kV
P.System Data 1
80 .. 125 V
P.System Data 1
0.10 .. 9.99
P.System Data 1
0.10 .. 9.99
P.System Data 1
(Setting options depend
on configuration)
P.System Data 1
(Setting options depend
on configuration)
P.System Data 1
(Setting options depend
on configuration)
P.System Data 1
(Setting options depend
on configuration)
P.System Data 1
(Setting options depend
on configuration)
P.System Data 1
(Setting options depend
on configuration)
P.System Data 1
(Setting options depend
on configuration)
P.System Data 1
(Setting options depend
on configuration)
P.System Data 1
(Setting options depend
on configuration)
P.System Data 1
(Setting options depend
on configuration)
P.System Data 1
(Setting options depend
on configuration)
P.System Data 1
0.01 .. 32.00 sec
Osc. Fault Rec.
Save w. Pickup
Save w. TRIP
Start w. TRIP
Osc. Fault Rec.
0.30 .. 5.00 sec
Osc. Fault Rec.
0.05 .. 0.50 sec
Osc. Fault Rec.
0.05 .. 0.50 sec
0.10 .. 5.00 sec; ∞
Osc. Fault Rec.
P.System Data 2
not reversed
reversed
Setting Options
Default Setting
1A
Terminal R7
200 A
1A
60.0
Terminal P7
200 A
1A
60.0
110.0 kV
100 V
0.00 °
110.0 kV
100 V
1.73
1.73
Q0
None
None
None
None
None
None
None
None
None
None
0.15 sec
Save w. Pickup
1.00 sec
0.10 sec
0.10 sec
0.50 sec
not reversed
Comments
CT rated secondary current IX2
Earthing electrod IX3 connected
to
CT rated primary current IX3
CT rated secondary current IX3
Factor: prim. over sek. current
IX3
Earthing electrod IX4 connected
to
CT rated primary current IX4
CT rated secondary current IX4
Factor: prim. over sek. current
IX4
VT Rated Prim. Voltage Set UL1,
UL2, UL3
VT Rated Sec. Voltage Set UL1,
UL2, UL3
Angle correction UL1, UL2, UL3 -
VT
VT Rated Primary Voltage U4
VT Rated Secondary Voltage U4
Matching ratio Phase-VT to
Open-Delta-VT
Matching ratio Ph-VT(U4) to
Open-DeltaVT
Switchgear / CBaux at Side 1
Switchgear / CBaux at Side 2
Switchgear / CBaux at Side 3
Switchgear / CBaux at Side 4
Switchgear / CBaux at Side 5
Switchgear / CBaux at Measur-
ing Loc. M1
Switchgear / CBaux at Measur-
ing Loc. M2
Switchgear / CBaux at Measur-
ing Loc. M3
Switchgear / CBaux at Measur-
ing Loc. M4
Switchgear / CBaux at Measur-
ing Loc. M5
Switchgear / CBaux at ext. loca-
tion 1
Minimum TRIP Command Dura-
tion
Waveform Capture
Max. length of a Waveform
Capture Record
Captured Waveform Prior to
Trigger
Captured Waveform after Event
Capture Time via Binary Input
sign of P,Q
7UT613/63x Manual
C53000-G1176-C160-2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents