Setting Notes - Siemens SIPROTEC 7UT613 series Manual

Differential protection
Hide thumbs Also See for SIPROTEC 7UT613 series:
Table of Contents

Advertisement

Figure 2-103
Logic diagram of the forward active power supervision

2.13.2 Setting Notes

General
Pickup Values
7UT613/63x Manual
C53000-G1176-C160-2
broken wire or voltage failure is recognised or voltage transformer protection breaker
failure (via the respective binary input) is indicated (see also Subsection "Technical
Data").
The application of forward power monitoring is only possible in 3-phase protected ob-
jects. It can only be assigned to a side of the main protected object or another mea-
suring location. Furthermore, it is a prerequisite that the device is connected to a three-
phase voltage transformer set, that permits a sensible calculation of the active power
with the respective current transformer connection.
The forward power monitoring can only be effective and is only accessible if it has
been set during configuration under address 151 FORWARD POWER = Enabled (sec-
tion 2.1.3).
Under address 5101 FORWARD POWER the forward power monitoring can be switched
ON or OFF. Furthermore, the command can be blocked during enabled monitoring
function (Block relay).
For undershooting of a preset active power and the exceeding of another preset active
power, one pickup value each must be set.
If the forward power monitoring has been assigned to a side of the protected object,
the pickup value can be set directly as reference value (with reference to the nominal
2.13 Forward Power Supervision
251