Inverse Time Overcurrent Protection - Siemens SIPROTEC 7UT613 series Manual

Differential protection
Hide thumbs Also See for SIPROTEC 7UT613 series:
Table of Contents

Advertisement

2 Functions
Figure 2-68
Logic diagram for the overcurrent stage 3I0> for residual current (simplified)
2.4.1.2

Inverse Time Overcurrent Protection

Pickup, Tripping
154
The pickup values of all stages I> (phases), 3I0> (zero sequence current), I>>
(phases), 3I0>> (zero sequence current) and the time delays associated for each
stage can be set individually.
The inverse-time overcurrent protection stages always operate with a characteristic
either according to the IEC or the ANSI standards or according to a user-defined char-
acteristic. The characteristics and their equations are displayed in the Technical Data.
When configuring one of the inverse time characteristics, definite time stages I>> and
I> are also enabled.
Each phase current and the zero sequence current (sum of phase currents) are com-
pared individually to a common setting value Ip or 3I0p. If a current exceeds the
setting value by 1.1 times, the corresponding stage picks up and is signalled selective-
ly. If inrush restraint is used, a frequency analysis is performed first. Depending on the
detection of inrush currents, either normal pickup annunciations or relevant inrush
messages are issued. For pickup, the RMS values of the fundamental harmonics are
used. During the pickup of an I
fault current by means of an integrating measuring procedure, depending on the se-
stage, the tripping time is calculated from the flowing
p
7UT613/63x Manual
C53000-G1176-C160-2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents