Emerson Fisher 4320 Instruction Manual page 42

Wireless position monitor
Hide thumbs Also See for Fisher 4320:
Table of Contents

Advertisement

4320 Position Monitor
February 2013
AMS Wireless Configurator or AMS Device Manager
In AMS Device Manager select Configure, Manual Setup, then select Resetting Power Module Variables from the Power
tab, as shown in figure 30 to reset the power module variables.
1. A warning will be displayed, noting this should only be done when a new power module is installed. Select Next if
you have replaced the power module. Select Cancel if the power module has not been replaced.
2. Select Yes when asked if you want to continue.
3. Press Next on the status screen displayed.
4. Select the installed power module type, Standard or Extended. Refer to figure 29 to identify the power module
type. Select Next to continue.
5. Select Next on the Power Module Date status screen to continue.
Note
When the device initially joins the network and the Power Module Date has not been updated, the first date captured will be
captured and stored. The power module date will be updated once the device is on the wireless network.
6. Select Next to complete the Resetting Power Module Variables procedure.
Figure 30. Resetting Power Module Variables
42
POWER MODULE DATE (INDICATES
DATE OF POWER MODULE INSTALLATION)
Instruction Manual
D103392X012
BATTERY LIFE
REMAINING
SELECT
RESET POWER
MODULE VARIABLES