Figure 29. Typical Warning Labels from Power Module
GE43564
STANDARD LIFE POWER MODULE

Removal

Refer to figure 2.
1. Loosen the two instrument cover screws and open the cover.
2. Remove the four screws providing the mechanical connection to the housing.
3. Remove the four larger electrical connection screws.
4. Remove the power module.

Installation

Refer to Installing Standard and Extended Life Power Modules on page 6. Recalibrate the instrument before putting it
back into service.

Resetting Power Module Variables

When power modules are replaced, you must reset Battery Life Remaining (shown in figure 30), which can be used for
scheduling maintenance of the power module. The counter can be reset using a Field Communicator or AMS Device
Manager. Resetting this value will also change the Power Module Date.
Note
The Power Module menu/Power tab is only available for a battery-powered device. It will not be displayed if the External Power
option is installed.
Field Communicator
Select Online, Configure, Manual Setup, Power Module, then Reset Module Data to reset Battery Life. Refer to the
Configure menu tree shown in figure 22.
Note
Reset Module Date can also be accessed by selecting Service Tools, Maintenance, and Power Module.
GE43565
EXTENDED LIFE POWER MODULE
4320 Position Monitor