Table 1. Specifications
Available Mountings
J
Quarter‐turn rotary‐shaft
J
sliding‐stem or
J
linear applications
Can also be mounted on other actuators that comply
with IEC 60534‐6‐1, IEC 60534‐6‐2, VDI/VDE 3845
and NAMUR mounting standards
Input Measurement
Stem Travel (linear movement)
Minimum: 2.5 mm (0.10 inch)
Maximum: 210 mm (8.25 inches)
Shaft Rotation (rotary movement)
Minimum: 45_
Maximum: 90_
Shaft Rotation (rotary movement, arced array)
Minimum: 13_
Maximum: 30_
Measurement Output
Analog: 0-100%
Discrete: on/off switches (2)
Reference Accuracy
1% of span
Local User Interface
Liquid Crystal Display (LCD)
Two pushbuttons for navigation, setup, and
calibration
Communication Protocol
HART 7
Input Communication Signal
WirelessHARTr communication
Initial Dynamic Variable Assignments
(Default)
Variable
Primary (PV)
Secondary (SV)
Tertiary (TV)
Quaternary (QV)
Refer to table 4 for a complete list of Device Variables
Variable Name
Position (Fixed)
Closed Limit Switch
Open Limit Switch
Temperature
Output Communication Signal
2.4 Ghz, DSSS, WirelessHART
Maximum 10 dBm EIRP at 2.46 GHz,
10 mW EIRP at 2.46 GHz
Wireless Classifications
Class A digital device, complies with part 15 of the
FCC Rules
Contains FCC ID: LW2RM2510
Contains IC: 2731A‐RM2510
Electromagnetic Compatibility
Meets EN 61326‐1 (First Edition)
Immunity—Industrial locations per Table 2 of
the EN 61326‐1 standard. Performance is
shown in table 2 below.
Emissions—Class A & B. Performance is shown in
table 3 below.
ISM equipment rating: Group 1, Class A & B
Vibration Testing
Meets or exceeds vibration levels specified in
ANSI/ISA 75.13.01 1996 (2007)— 4 mm peak to peak
at 5 Hz to 2 Gn from 15­150 Hz and 1 Gn from
150­ 2000 Hz
European Directive Information
This product complies with the following directives:
ATEX Directive (94/9/EC)
Electro Magnetic Compatibility (EMC) (2004/108/EC)
Radio and Telecommunications Terminal Equipment
Directive (R&TTE) (1999/5/EC)
Refer to the Safety Instructions (D103022X012) for
the Declaration of Conformity
Operating Temperature Limits
-40 to 80_C (-40 to 176_F)
LCD may not be readable below -20_C (-4_F)
Temperature Sensitivity
0.06% change per degree C
Storage Temperature Limits
Upper limit not to exceed 100_C (212_F)
Humidity Limits
10-95% Non‐Condensing Relative Humidity