UPS5000-E-(25 kVA-125 kVA)-FM
User Manual
Configuration

2.4.1 Single UPS

The UPS5000-E uses a modular design in which multiple power modules are connected in
parallel to deliver a high loading capacity. If a single power module is faulty, the other power
modules continue working. When the load power is small, even a single UPS can provide
redundant capacity, which ensures high reliability.

2.4.2 Parallel System

In a parallel system, the mains input, bypass input, and AC output terminals between cabinets
are connected in parallel. Energy control modules (ECMs) on each UPS are connected over
parallel cables. The parallel connections synchronize the UPS outputs to supply power to
loads. If one UPS fails, the other UPSs continue supplying power to loads.
a conceptual diagram of an N+X parallel system.
Issue 02 (2017-10-23)
Application Scenario
equipment rooms and data centers.
In addition to common parallel system advantages, the dual-bus
system also provides outstanding availability and eliminates
bottleneck failures. However, configuration of the dual-bus system is
complex.
A 1+1 parallel system is a typical configuration. You can set the number of requisite UPSs and
redundant ones on the LCD or WebUI.