Huawei UPS5000-E-****-FM series User Manual page 251

25 kva-125 kva
Hide thumbs Also See for UPS5000-E-****-FM series:
Table of Contents

Advertisement

UPS5000-E-(25 kVA-125 kVA)-FM
User Manual
Alarm
ID
(Alarm
ID-Caus
e ID)
0088-1
0089-1
0090-1
0090-2
0356
0359
0332
0334
Issue 02 (2017-10-23)
Alarm
Severit
Name
y
bypass
Rack
Critical
address
conflict
Rack
Minor
output
overload
Dry contact
Critical
board fault
Battery
Minor
Mode
No power
Warning
supplied
Output
Minor
disabled
BSC
Warning
master
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Cause
Solution
UPS is not
bypass mode.
normal, and
transfers to
bypass mode.
The
Check the rack address setting.
configured
rack address
conflicts with
another one.
The load
Check the load and remove
is
some loads or expand the UPS
excessive.
power capacity if the UPS is
overloaded.
The rack
capacity
Check that the configured rack
setting is
capacity meets requirements.
not
appropriat
e.
I2C
Replace the dry contact board
communicati
MUE05A.
on with the
dry contact
board
MUE05A
fails.
I2C
Replace the dry contact board
communicati
MUE06A.
on with the
dry contact
board
MUE06A
fails.
The UPS is
The running status is displayed. See
working in
details about how to handle other
battery mode.
alarms.
No power is
The running status is displayed. See
supplied.
details about how to handle other
alarms.
The output is
The running status is displayed. See
disabled.
details about how to handle other
alarms.
BSC master
The running status is displayed. No
system.
further measures are required.
C Alarm List