If an incorrect password is entered three consecutive times, the account will be locked out for 5 minutes.
If the power module receives a startup command when it cannot be started, the startup command will be
kept for 1 minute. If the startup command is not cleared within 1 minute (for example, other faults occur
on the module, or shutdown or fault rectification is performed) and the module can be started, the
module responds to the startup command.
Step 6 Ensure that the UPS transfers to normal mode. View the system running diagram to check that
the Bypass mode alarm disappears on the LCD. Check the UPS three-phase output voltage
and frequency by viewing the AC Output data on the LCD, as shown in
Figure
Issue 02 (2017-10-23)
Figure 5-11 WebUI login
e.
On the homepage, choose Monitoring > Control, and click Inv. ON. In the
displayed dialog box, click OK to start the inverter, as shown in
Figure 5-12 Starting the inverter
5-14. Use a multimeter to measure the three-phase output voltage and frequency.