Monitoring Interface Card - Huawei UPS5000-E-****-FM series User Manual

25 kva-125 kva
Hide thumbs Also See for UPS5000-E-****-FM series:
Table of Contents

Advertisement

UPS5000-E-(25 kVA-125 kVA)-FM
User Manual
Silk
Screen
0V
SPD
0V
Functions
The dry contact card allows the UPS to detect and manage the switch status of the battery
system (including the external battery switch) and implement remote emergency power-off
(EPO).
Specifications

2.3.5.4 Monitoring interface card

The monitoring interface card provides external ports as well as monitoring and control
functions for the MDU. The ports include the ambient temperature and humidity sensor port,
iBAT 2.0 port, FE port, battery temperature monitoring port, and network management port.
Issue 02 (2017-10-23)
Description
Port for monitoring the
input AC surge protective
device (SPD)
Port for signal ground
The dry contact interface card takes effect only after it is set on the monitoring system. Set the
unused dry contact signal to the unused status.
Set the EPO port to NO or NC as required.
When multiple UPSs are paralleled, all dry contact signals to be used need to connect to each UPS.
Single cables require dual-insulated twisted cables. If the length of a power cable is within 25–50 m,
its cross-sectional area must be 0.5 mm
Hot-swappable
0.5 U high
The FE port resembles the RS485 port. Follow the silk screen when connecting
communications cables as, if the RS485 port is mistaken for the FE port during cable
connection, the WebUI cannot be connected. Conversely, if the FE port is mistaken for the
RS485 port during cable connection, RS485 communication fails.
If MDU communication fails, the "Comm. failure" message is displayed on the LCD,
screen switching is disabled, the buzzer buzzes, and the fault indicator is red. Once the
fault is rectified, the LCD recovers, and the alarm is cleared.
Dry contact signals take effect after you set them. Disable unused dry contact signals on
the monitoring system.
In a parallel system, ensure that used dry contacts properly connect to each UPS.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Status
Connected: SPD
enabled
Disconnected:
SPD disabled
2
2
to 1.5 mm
.
2 Overview
Initial Status
Connected
26

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups5000-e-125k-fm

Table of Contents