Huawei UPS5000-E-****-FM series User Manual page 53

25 kva-125 kva
Hide thumbs Also See for UPS5000-E-****-FM series:
Table of Contents

Advertisement

UPS5000-E-(25 kVA-125 kVA)-FM
User Manual
Port
Descript
ion
Table 3-4
Table 3-4 Upstream input switch configurations
Upstream
Input
Switch
Mains
input
Bypass
input
Table 3-5 Recommended upstream input and downstream output circuit breakers
Model
UPS5000-E-1
25K-FM
Issue 02 (2017-10-23)
Connection
Bolt
Method
Specificat
ions
terminals
lists the recommended upstream input switch configurations.
25 kVA
50 kVA
63 A/3P
100 A/3P
63 A/3P
100 A/3P
UPS
Capacity
25 kVA
50 kVA
75 kVA
100 kVA
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Bolt Hole
Diameter
75 kVA
160 A/3P
160 A/3P
Component
Mains input circuit
breaker
Bypass input circuit
breaker
Downstream output
circuit breaker
Mains input circuit
breaker
Bypass input circuit
breaker
Downstream output
circuit breaker
Mains input circuit
breaker
Bypass input circuit
breaker
Downstream output
circuit breaker
Mains input circuit
3 Installation
Bolt Length
Torque
100 kVA
125 kVA
200 A/3P
250 A/3P
200 A/3P
250 A/3P
Specification
Manufactur
s
er
T1N160 TMD
ABB
R63 FFC 3P
(recommende
d when the
T1N160 TMD
short-circuit
R63 FFC 3P
current where
the switch is
T1N160 TMD
located is
R63 FFC 3P
less than 6
kVA.)
T1N160 TMD
ABB
R100 FFC 3P
(recommende
d when the
T1N160 TMD
short-circuit
R100 FFC 3P
current where
the switch is
T1N160 TMD
located is
R100 FFC 3P
less than 36
kVA.)
T1N160 TMD
R160 FFC 3P
T1N160 TMD
R160 FFC 3P
T1N160 TMD
R160 FFC 3P
T3N250 TMD
45