Huawei UPS5000-E-****-FM series User Manual page 253

25 kva-125 kva
Hide thumbs Also See for UPS5000-E-****-FM series:
Table of Contents

Advertisement

UPS5000-E-(25 kVA-125 kVA)-FM
User Manual
Alarm
ID
(Alarm
ID-Caus
e ID)
0095-1
0096-1
0098-1
Issue 02 (2017-10-23)
Alarm
Severit
Name
y
Insuffi.
Minor
redundancy
ECO volt.
Minor
Abnormal
Bypass
Minor
current not
shared
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Cause
Solution
of
redundant
racks is
incorrect.
1. Reduce the load.
The load
is
2. Decrease the configured number
excessive.
of redundant modules.
The
configure
d number
of
redundant
modules
is
incorrect.
1. Check the bypass input voltage
The ECO
and frequency.
bypass
voltage or
2. Check that the rated voltage,
frequency
rated frequency, ECO bypass
is out of
voltage range, and frequency
the preset
range are correctly set.
range.
3. Check that the bypass cables
and circuit breakers are
The ECO
correctly connected.
bypass
voltage or
frequency
range is
incorrectl
y set.
The
bypass
input
sequence
is reverse
or the
neutral
wire is
disconnec
ted.
1. Check that the output and
The
bypass input circuit breakers on
output
each rack are ON.
and input
circuit
2. Check that bypass input and
breakers
output power cables on each
are OFF.
rack meet the length
requirements.
The
C Alarm List
245