Figure 5-26 Starting a shallow discharge test
----End

5.6.3 Capacity Test

Context
Before a capacity test, ensure that:
Procedure
Step 1 On the main screen of the LCD, tap System Info. Tap
displayed.
Issue 02 (2017-10-23)
When the battery test is complete, the test data is used as common test data. Record the data obtained
from the latest five tests.
The shallow discharge test automatically stops in any of the following cases:
The battery discharge capacity reaches the specified value (10%–50%, 20% by default).
The discharge voltage reaches the warning threshold (calculated in real time).
The load ratio fluctuation exceeds 10%.
An alarm is generated.
The UPS is working in normal mode; float charging or hibernation has lasted for 2 hours
after the state of charge (SOC) reaches 100%; and the load ratio fluctuation is less than
10%.
The UPS has generated no battery overtemperature, overvoltage, or overcurrent alarm. No
generator is connected to the UPS.
The mains, batteries, charger, and discharger are normal. No overload alarm is generated.