UPS5000-E-(25 kVA-125 kVA)-FM
User Manual
Procedure
Step 1 On the main screen of the LCD, tap System Info. Tap
displayed.
Step 2 On the Maintenance screen, tap Battery Maint..
Figure 5-24 Maintenance screen
Step 3 Tap Start next to Forced Equalized Charging to start a forced equalized charging test.
Figure 5-25 Starting a forced equalized charging test
Issue 02 (2017-10-23)
The mains input is normal.
Batteries are properly connected.
Batteries are not in the equalized charging state.
The forced equalized charging test automatically stops in any of the following cases:
The forced equalized charging test duration reaches the forced equalized charging protection time
(12–24 h, 18 h by default).
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Operations
. The Maintenance screen is
184