Huawei UPS5000-E-****-FM series User Manual page 204

25 kva-125 kva
Hide thumbs Also See for UPS5000-E-****-FM series:
Table of Contents

Advertisement

UPS5000-E-(25 kVA-125 kVA)-FM
User Manual
Step 3 Check that the EPO alarm is cleared by viewing active alarms. If the system bypass input is
normal, the UPS transfers to bypass mode.
Issue 02 (2017-10-23)
Figure 5-41 Clearing faults
Viewing active alarms on the LCD
Choose System Info > Alarms and tap Active Alarms to check that the EPO alarm is
cleared.
Figure 5-42 Active alarms
Viewing active alarms on the WebUI
In a web browser, enter the UPS IP address and select a display language. Enter a user
name and password, and click Login to open the homepage. Choose Monitoring >
Active Alarms to check that the EPO alarm is cleared. If the bypass input is normal, the
UPS transfers to bypass mode.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Operations
196