Step 7 Verify that the actual battery capacity and number of cells are consistent with the
corresponding values set on the LCD. (A 2 V battery is a cell. If a battery is 12 V, the number
of cells is equal to the number of batteries multiplied by 6. If a battery is 2 V, the number of
cells is equal to the number of batteries.) Use a multimeter to check that the sum of the
absolute voltage of the negative battery string and the voltage of the positive battery string is
greater than a certain value (2 x number of cells) to ensure that the battery strings are
connected properly.
Number of cells indicates the number of 2 V cells connected to the UPS. Number of cells
affects the charge voltage and discharge time. An incorrect setting will cause a high or low
charge voltage, which greatly shortens the battery lifespan. Moreover, the UPS may shut
down before the discharging is completed, which may result in data backup failure.
lists examples of setting battery parameters.