UPS5000-E-(25 kVA-125 kVA)-FM
User Manual
Figure 4-67 CIM control
Item
Reset
Blink
Internal resistance
Bus Capa. Life
If the service life of a capacitor is about to end, that is, Module X bus capacitor life (y) is less
than 1.0, contact Huawei technical support to replace the power module.
Issue 02 (2017-10-23)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Description
If there is abnormal data, you can reset.
Make the red indicator on the BIM start or
stop blinking super fast.
Measure the battery internal resistance. If
the condition for measuring internal
resistance is met (batteries are fully
charged), you can tap Measure to start
measuring the internal resistance of the
selected BIM in a CIM. When the BIM
number is 0, the whole internal resistances
of the BIMs in a selected CIM can be
measured.
NOTE
The interval between two measurement
operations must be greater than 10 minutes.
4 User Interface
137