2920 Float & Tape Transmitter
88
Config Params
Response Delay
2nd TX Address
2nd Level Ref
2nd Temp Ref
3rd TX Address
3rd Level Ref
3rd Temp Ref
5 Display and Configuration Interface
The default for the L&J response delay is 2 mS.
Set this Address between 1 and 127 to have the
transmitter respond to a 2nd TankWay address. This
Address must be different than the Unit Addr (Basic
Setup) and the 3rd TX Address. Also, this address must
be different than all other transmitters on the same L&J
TankWay bus. The default value is 0 which means the
transmitter will not respond.
This is set if the transmitter needs to respond to the a
second L&J TankWay address. This allows the
transmitter to send additional data items.
If the 2nd TX Address is set, this selects the data item in
the transmitter to be sent as the level portion of the L&J
TankWay message. The Encoder Type (Basic Setup)
determines the data range and resolution.
• 2000: 0 to 96 with a resolution of 0.01
• 1000/1500 Type 3: 0 to 255.9 with a resolution of
0.02
• 1000/1500 Type 4: 0 to 170.66 with a resolution of
0.003
This is set if the transmitter needs to respond to the a
second L&J TankWay address. This allows the
transmitter to send additional data items.
If the 2nd MS Address is set, this selects the data item in
the transmitter to be sent as the temperature portion of
the L&J TankWay message. This parameter is
transmitted in the range -819.0 to 819.0 with 0.1
resolution.
Set this Address between 1 and 127 to have the
transmitter respond to a 3rd L&J TankWay address. This
Address must be different than the Unit Addr (Basic
Setup) and the 2nd TX Address. Also, this address must
be different than all other transmitters on the same L&J
TankWay bus. The default value is 0 which means the
transmitter will not respond.
If the 3rd TX Address is set, this selects the data item in
the transmitter to be sent as the level portion of the L&J
TankWay message. The Encoder Type (Basic Setup)
determines the data range and resolution.
• 2000: 0 to 96 with a resolution of 0.01
• 1000/1500 Type 3: 0 to 255.9 with a resolution of
0.02
• 1000/1500 Type 4: 0 to 170.66 with a resolution
of 0.003
If the 3rd MS Address is set, this selects the data item in
the transmitter to be sent as the temperature portion of
the L&J TankWay message. This parameter is
transmitted in the range -819.0 to 819.0 with 0.1
resolution.