Varec 2920 Installation And Operation Manual page 172

Float & tape transmitter
Table of Contents

Advertisement

2920 Float & Tape Transmitter
162
Register Number
206
Reserved
208
Reserved
210
211
212 - 214
Reserved
215
-
217- 219
Reserved
220
221
222 - 224
Reserved
225
226
227 - 229
Reserved
230
232
234
236
238
240
Type
Integer
AlmStat (Bit Field) (Tank Data > AlmStat)
Integer
DiagStat (Bit Field) (Tank Data > DiagStat)
Reserved
Coded
Level Units (Local Display)
44 - Feet
45 - Meters
47 - Inches
49 - Millimeters
240 - 16ths
241 - Ft-In-16ths
243 - Ft-In-8ths
Coded
Temp Units (Local Display)
33 - F
32 - C
Reserved
Coded
Level Type (Basic Setup > Enc Direction)
0 - Forward
1 - Reverse
Coded
Temp Type (Basic Setup > RTD Type)
0 - Pt100
1 - Cu100
2 - Cu90
3 - None
Reserved
Coded
Gauge Type (Basic Setup > Gauge Type)
0 - Metric
1 - English
Coded
Power Control (Basic Setup > Control)
11 - On
12 - Off
Reserved
Float
Crit Low Level (MODBUS > CritLowLevel)
Float
Adv Low Level (MODBUS > AdvLowLevel)
Float
Adv High Level (MODBUS > AdvHighLevel)
Float
Crit High Level (MODBUS > CritHighLevel)
Float
Level Deadband (MODBUS > LDeadband)
Float
Crit Low Temp (MODBUS > CritLowTemp)
MODBUSAppendix A — MODBUS Implementation
Description
Installation and Operations Manual

Advertisement

Table of Contents
loading

Related Products for Varec 2920