Varec 2920 Installation And Operation Manual page 78

Float & tape transmitter
Table of Contents

Advertisement

2920 Float & Tape Transmitter
68
To Access Tank Data:
1. Press Enter to access the Main Menu. The System Menu point is automatically highlighted.
Main Menu
06
Tank Data
Digital Outputs
Analog Inputs
2. Press Minus six times to move the highlight to Tank Data.
3. Press Enter and the Tank Data menu opens.
4. To select one of the options, press Minus to move the highlight to the option you want and
then press Enter.
Refer to the table below for more information on each Tank Data option.
Display Only
Level
Temp
AlmStat
DiagStat
PntStat
Lev Disp Units
Temp Disp Units
Elapse
Display Only
Config Params
All Params
Description
Indicates the current measured or calculated level after
corrections are applied.
Indicates the current product temperature.
Integer value indicating any alarm conditions, as follows:
0x0001: Critical Low Level
0x0002: Advisory Low Level
0x0004: Advisory High Level
0x0008: Critical High Level
0x0010: Critical Low Temperature
0x0020: Advisory Low Temperature
0x0040: Advisory High Temperature
0x0080: Critical High Temperature
0x0100: Digital Input 1
0x0200: Digital Input 2
0x0400: Digital Input 3
0x0800: Digital Input 4
Integer Value indicating any diagnostic alarm conditions,
as follows:
0x0001: Invalid Level
0x0002: Invalid Temperature
Integer value indicating status of point, as follows:
0: No Errors
Indicates which units will be used for level values
Indicates which units will be used for temperature
values
Time of last update.