6. Select Analog Output #1.
7. Monitor the 4-20 mA meter, and Press the E button.
8. Enter the value from the 4-20 mA Meter into the Cal. Point #1.
9. Repeat this process for calibration points 2 through 5.
10. Press the C button twice to exit to the main menu
11. Select Analog Output from the main Menu on the 2920.
12. Select Analog Output #1.
13. Scroll to the Commands menu.
14. Scroll the menu to the Value parameter.
15. Enter values 0 to 100 (percent) and verify the measurement on the 4-20 mA Meter:
0.0 = 4.00 +/- 0.01
25.0 = 8.00 +/- 0.01
50.0 = 12.00 +/- 0.01
75.0 = 16.00 +/- 0.01
100.0 = 20.00 +/- 0.01
Output Calibration of Channel 2
1. Connect terminals A+24V and AO2+.
2. Connect a calibrated 4-20 mA Meter to terminals AO2- & AI COM.
3. If the 24VDC Output Power Supply is turned off (default), turn it on using the following
steps:
a. Select the Basic Setup from the main Menu on the 2920.
b. Scroll to the Config Params menu.
c. Scroll to the Control parameter.
d. Set the control parameter to On.
4. Select Calibration from the main Menu on the 2920.
5. Select Analog Output.
6. Select Analog Output #2.
7. Monitor the 4-20 mA meter, and Press the E button.
8. Enter the value from the 4-20 mA Meter into the Cal. Point #1.
9. Repeat this process for calibration points 2 through 5.
10. Press the C button twice to exit to the main menu
11. Select Analog Output from the main Menu on the 2920.
12. Select Analog Output #2.
13. Scroll to the Commands menu.
14. Scroll the menu to the Value parameter.
5 Display and Configuration Interface