Varec 2920 Installation And Operation Manual page 101

Float & tape transmitter
Table of Contents

Advertisement

Varec, Inc.
Config Params
Addr
Manuf ID
Device Type
Device ID
Preambles Cmd
Frame Format
Temp Disp Units
Level Disp Units
Access Code
No. of Elem
Type of Spacing
Elem Spacing
Element #1 Pos through
Element #16 Pos
Bottom
Level Offset
Select Element
Zero
Span
Override Short
Override Open
The short HART address used to detect this device.
The Unique ID of the Manufacturer that build the HART
device. For NMT and FMR, this is 17 - E+H.
The unique device type specified by the HART device
manufacturer. For FMR, 0 to 49; for NMT, 180 to 199.
The long HART ID number read from the HART device,
containing manufacturer, device type and ID number.
The number of Preambles in the Request.
Type of message framing supported by the NMT.
Temperature displayed units used by the NMT.
Level displayed units used by the NMT.
Access code to allow the parameters in the NMT to be
changed. Code 530 unlocks the NMT while any other
code locks it.
Specifies the number of measuring elements connected
to the NMT.
Indicates if the measuring elements connected to the
NMT are spaced at regular or irregular intervals:
• Regular: Element spacing value is used between
each element.
• Irregular: Allows the position of each element to be
individually set.
When element interval type is set to regular, this value
specifies the distance between each element.
Position of element #1 through element #16
The bottom point specifies the level of the lowest
temperature element inside the tank, this is then used
as the reference to determine which elements are
covered at a specific liquid level.
An element is only used for the average liquid
temperature calculation when it is this distance below
the liquid level.
Specifies a particular element for calibration.
Used to adjust the average temperature calculation
zero.
Used to adjust the average temperature calculation
span.
Short Circuit Error Value: When a short-circuit fault is
detected on an element, this error value is returned
instead of the normal measured temperature.
Open Circuit Error Value: When an open-circuit fault is
detected on an element, this error value is returned
instead of the normal measured temperature.
5 Display and Configuration Interface
91