Varec 2920 Installation And Operation Manual page 87

Float & tape transmitter
Table of Contents

Advertisement

Varec, Inc.
4. Select either Analog Out #1 or Analog Out #2.
Note The parameters for Analog Out #1 and Analog Out #2 are identical. However, each
Analog Out can be configured differently. Analog Out #1 is used as an example below.
5. To select one of the options, press Minus to move the highlight to the option you want and
then press Enter.
Refer to the table below for more information on each Analog Out option.
Display Only
RefValue
Percent Range
Elapse
Pnt Status
Pnt CheckSum
Commands
Command
Raw Value
Value
Description
Displays the data value from the PntRef data item.
When the Control is set to enable, this value control the
AO output value.
Displays the percent of range for the analog output
value. A 0 percent is 4 mA, and 100 is 20 mA.
Time of last update.
Byte value indicating status of point. Values are:
0: No error
CRC-16 Checksum of point's static configuration
parameters.
Used to reset the calibration curve back to factory
default values.
This value is set to manually control the 4-20 mA output.
Setting the Raw Value does not apply the calibration
correction to the signal.
This value is set to manually control the 4-20 mA output.
Setting the Value applies the calibration correction (if
available) to the output signal.
5 Display and Configuration Interface
77