Varec, Inc.
Config Params
Response Delay
2nd TX Address
2nd Level Ref
2nd Temp Ref
3rd TX Address
3rd Level Ref
3rd Temp Ref
All Params
5 Display and Configuration Interface
30
Set this Address between 1 and 999 to have the
transmitter respond to a 2nd Mark/Space address. This
Address must be different than the Unit Addr (Basic
Setup) and the 3rd MS Address. Also, this address must
be different than all other transmitters on the same
Mark/Space bus. The default value is 0 which means the
transmitter will not respond.
This is set if the transmitter needs to respond to the a
second Mark/Space address. This allows the transmitter
to send additional data items.
If the 2nd MS Address is set, this selects the data item in
the transmitter to be sent as the level portion of the
Mark/Space message. Depending on the transmitter
Data Mode (Basic Setup), this parameter is transmitted
in the range up to 0 to 80 with 0.001 resolution.
This is set if the transmitter needs to respond to the a
second Mark/Space address. This allows the transmitter
to send additional data items.
If the 2nd MS Address is set, this selects the data item in
the transmitter to be sent as the temperature portion of
the Mark/Space message. This parameter is transmitted
in the range -799.9 to 799.9 with 0.1 resolution.
Set this Address between 1 and 999 to have the
transmitter respond to a 3rd Mark/Space address. This
Address must be different than the Unit Addr (Basic
Setup) and the 2nd MS Address. Also, this address must
be different than all other transmitters on the same
Mark/Space bus. The default value is 0 which means the
transmitter will not respond.
If the 3rd MS Address is set, this selects the data item in
the transmitter to be sent as the level portion of the
Mark/Space message. Depending on the transmitter
Data Mode (Basic Setup), this parameter is transmitted
in the range up to 0 to 80 with 0.001 resolution.
If the 3rd MS Address is set, this selects the data item in
the transmitter to be sent as the temperature portion of
the Mark/Space message. This parameter is transmitted
in the range -799.9 to 799.9 with 0.1 resolution.
Lists all Display, Commands, and Config Params in a list.