Varec 2920 Installation And Operation Manual page 82

Float & tape transmitter
Table of Contents

Advertisement

2920 Float & Tape Transmitter
72
Config Params
DOPwrUpState
DO1 Assignment
DO2 Assignment
DO3 Assignment
DO4 Assignment
Duration1
Duration2
All Params
5 Display and Configuration Interface
This parameter is used to force a Relay to be active at
startup.
0x0001: If Controlled at Startup, Relay 1 will be set to
Active
0x0002: If Controlled at Startup, Relay 2 will be set to
Active
0x0004: If Controlled at Startup, Relay 3 will be set to
Active
0x0008: If Controlled at Startup, Relay 4 will be set to
Active
0x0010: Relay 1 Is Controlled at Startup
0x0020: Relay 2 Is Controlled at Startup
0x0040: Relay 3 Is Controlled at Startup
0x0080: Relay 4 Is Controlled at Startup
These parameters are used to assign the control and
activation source for the output relays.
0: Not Assigned
1: Host Interface
2: Critical High Level
3: Advisory High Level
4: Advisory Low Level
5: Critical Low Level
6: Critical High Temperature
7: Advisory High Temperature
8: Advisory Low Temperature
9: Critical Low Temperature
Sets the duration of Digital Output 1. If set to a non-zero
value, when the Relay activates, the relay activates for
the amount of time (in seconds) specified by the
duration then the relay deactivates. Setting the value to
zero, means the relay stays active indefinitely. The
default value is 0.
Sets the duration of Digital Output 2. If set to a non-zero
value, when the Relay activates, the relay activates for
the amount of time (in seconds) specified by the
duration then the relay deactivates. Setting the value to
zero, means the relay stays active indefinitely. The
default value is 0.
Lists all Display, Commands, and Config Params in a list.
Installation and Operations Manual