Analog Outputs

Here, the deadband is "shifted" due to the 50 Hz limitation. The command
frequency from 0 to 3 volts on the analog input will be 15 Hz. After 3 volts, the
frequency will increase at a rate of 0.2 volts per hertz up to 9 volts. After 9 volts
on the analog input the frequency command will remain at 45 Hz.
Explanation
Each drive has one or more analog outputs that can be used to annunciate a wide
variety of drive operating conditions and values.
The user selects the analog output source by setting [Analog Out Sel].
342
[Analog Out1 Sel]
345
[Analog Out2 Sel]
Vector
Selects the source of the value that drives the analog
output.
Options
0
"Output Freq"
1
"Command Freq"
1*
"Command Spd"
2
"Output Amps"
3
"Torque Amps"
4
"Flux Amps"
5
"Output Power"
6
"Output Volts"
7
"DC Bus Volts"
(1)
8
"PI Reference"
9
"PI Feedback"
10
"PI Error"
11
"PI Output"
12
"%Motor OL"
13
"%Drive OL"
14*
"CommandedTrq"
(1)
15*
"MtrTrqCurRef"
16*
"Speed Ref"
17*
"Speed Fdbk"
(1)
18*
"Pulse In Ref"
(1)
19*
"Torque Est"
(1)
20-23**
"Scale Block1-4"
(1)
24**
"Param Cntl"
* Vector Control Option Only
(1)
Refer to Option Definitions in User Manual.
Configuration
The PowerFlex 70 standard I/O analog output is permanently configured as a
0-10 volt output. The output has 10 bits of resolution yielding 1024 steps. The
analog output circuit has a maximum 1.3% gain error and a maximum 7 mV
offset error. For a step from minimum to maximum value, the output will be
within 0.2% of its final value after 12ms.
The PowerFlex 700 standard I/O analog output is permanently configured as a
0-10 volt output. The output has 10 bits of resolution yielding 1024 steps. The
analog output circuit has a maximum 1.3% gain error and a maximum 100 mV
offset error. For a step from minimum to maximum value, the output will be
within 0.2% of its final value after 12ms.
Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013
Default:
Options:
[Analog Out1 Lo] Value
[Analog Out1 Hi] Value
Param. 341 = Signed
Param. 341 = Absolute
–[Maximum Speed]
0 Hz
+[Maximum Speed]
–[Maximum Speed]
0 Hz
+[Maximum Speed]
–[Maximum Speed]
0 Hz/RPM
+[Maximum Speed]
0 Amps
0 Amps
200% Rated
–200% Rated
0 Amps
200% Rated
0 Amps
0 Amps
200% Rated
0 kW
0 kW
200% Rated
0 Volts
0 Volts
120% Rated Input Volts
0 Volts
0 Volts
200% Rated Input Volts
–100%
0%
100%
–100%
0%
100%
–100%
0%
100%
–100%
0%
100%
0%
0%
100%
0%
0%
100%
–800% Rated
0%
800% Rated
–200% Rated
0%
200% Rated
–[Maximum Speed]
0 Hz/RPM
+[Maximum Speed]
–[Maximum Speed]
0 Hz/RPM
+[Maximum Speed]
–25200.0 RPM
0 Hz/RPM
+[Maximum Speed]
–800%
0%
+800%
**Vector firmware 3.001 & later
Analog Outputs
0 "Output Freq"
001
002
See Table
003
004
005
007
006
012
135
136
137
138
220
219
377
378