10
8
6
4
2
0
6
12
18
Analog Scaling
[Speed Reference A Sel] = "Analog In 1"
[Analog In 1 Hi]
[Speed Ref A Hi]
10V
0 Hz
[Analog In 1 Lo]
[Speed Ref A Lo]
0V
60 Hz
Configuration #5:
• [Anlg In Config], bit 0 = "0" (Voltage)
• [Speed Ref A Sel] = "Analog In 1"
• [Speed Ref A Hi] = 60 Hz
• [Speed Ref A Lo] = 0 Hz
• [Analog In 1 Hi] = 5V
• [Analog In 1 Lo] = 0V
This configuration is used when the input signal is 0-5 volts. Here, minimum
input (0 Volts) represents 0 Hz and maximum input (5 Volts) represents 60 Hz.
This allows full scale operation from a 0-5 volt source.
6
5
4
3
2
1
0
6
12
18
Analog Scaling
[Speed Reference A Sel] = "Analog In 1"
[Analog In 1 Hi]
[Speed Ref A Hi]
5V
60 Hz
[Analog In 1 Lo]
[Speed Ref A Lo]
0V
0Hz
Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013