Allen-Bradley PowerFlex 70 Reference Manual page 88

Adjustable frequency ac drives
Hide thumbs Also See for PowerFlex 70:
Table of Contents

Advertisement

Digital Outputs
88
PowerFlex 70 Digital Output Selection
380
[Digital Out1 Sel]
[Digital Out2 Sel]
384
Selects the drive status that will energize a (CRx)
output relay.
(1)
Contacts shown in the Installation Instructions
are in drive powered state with condition not
present. For functions such as "Fault" and
"Alarm" the normal relay state is energized and
N.O. / N.C. contact wiring may have to be
reversed.
The selections can be divided into three types of annunciation.
1. The relay changes state due to a particular status condition in the drive.
The following drive conditions or status can be selected to cause the relay
activation:
Condition
Description
Fault
A drive Fault has occurred and stopped the drive
Alarm
A Drive Type 1 or Type 2 Alarm condition exists
Ready
The drive is powered, Enabled and no Start Inhibits exist. It is "ready" to run
Run
The drive is outputting Voltage and frequency to the motor (indicates 3–wire control, either
direction)
Forward Run
The drive is outputting Voltage and frequency to the motor (indicates 2–wire control in
Forward)
Reverse Run
The drive is outputting Voltage and frequency to the motor (indicates 2–wire control in Reverse)
Reset/Run
The drive is currently attempting the routine to clear a fault and restart the drive
Powerup Run
The drive is currently executing the Auto Restart or "Run at Power Up" function
DC Braking
The drive is currently executing either a "DC Brake" or a "Ramp to Hold" Stop command and the
DC braking voltage is still being applied to the motor.
Current Limit
The drive is currently limiting output current
Economize
The drive is currently reducing the output voltage to the motor to attempt to reduce energy costs
during a lightly loaded situation.
Mtr Overload
The drive output current has exceeded the programmed [Motor NP FLA] and the electronic
motor overload function is accumulating towards an eventual trip.
Power Loss
The drive has monitored DC bus voltage and sensed a loss of input AC power that caused the DC
bus voltage to fall below the fixed monitoring value (82% of [DC bus Memory]
Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013
Default:
1
"Fault"
4
"Run"
(1)
Options:
1
"Fault"
(1)
2
"Alarm"
3
"Ready"
4
"Run"
5
"Forward Run"
6
"Reverse Run"
7
"Auto Restart"
8
"Powerup Run"
9
"At Speed"
10
"At Freq"
11
"At Current"
12
"At Torque"
13
"At Temp"
14
"At Bus Volts"
15
"At PI Error"
16
"DC Braking"
17
"Curr Limit"
18
"Economize"
19
"Motor Overld"
20
"Power Loss"
21
"Input 1 Link"
22
"Input 2 Link"
23
"Input 3 Link"
24
"Input 4 Link"
25
"Input 5 Link"
26
"Input 6 Link"
381
385
389
382
386
390
383
002
001
003
004
218
012
137
157
147
053
048
184