Start-Up
B
6-0
Start-Up
6. Strt,Stop,I/O
This section
defines I/O
functions
including Start
and Stop.
6-2
B
Start-Up
A. Dig Inputs
Digital Input
Config options:
<Easy Configure>
Custom Configure
More info
Easy Configure
DigIn 5,6 = MOP
Inc, Dec?
Yes
6-3
Start-Up
A. Dig Inputs
Digital Inputs
1-4 will be set
to defaults.
Backup
6-10
Note:
- For V/Hz mode, states 6-3 - 6-5, & 6-11 - 6-16 are not displayed.
192
Figure 54 PowerFlex 700 Vector Control Option Startup (6)
6-1
Start-Up
6. Strt,Stop,I/O
Complete these
steps in order:
<A.Dig Inputs>
C.Analog
B.Dig Outputs
C.Analog Outputs
A. Dig Inputs
D.Done
Custom Configure
Start-Up
6-26
More
A. Dig Inputs
info
Easy Configure
asks questions
before writing
to digital ins.
Custom Configure
allows you to
No
program each
digital input(s)
B
6-4
Start-Up
A. Dig Inputs
Digital Inputs
1-6 will be set
to defaults.
Backup
No
Start-Up
A. Dig Inputs
2 wire control
uses a contact
that acts as
both STOP (Open)
& Run (Closed).
3 wire control
uses 2 contacts;
one for START
& one for STOP.
6-8
B
Start-Up
A. Dig Inputs
Enter choice for
More
Control Method
Info..
<3 wire>
2 wire
More info
2-wire
3-wire
6-9
B
B
6-11
Start-Up
Start-Up
A. Dig Inputs
A. Dig Inputs
Digital In1 set
Digital In1 set
to Not Used.
to Stop.
Digital In2 set
Digital In2 set
to Run/Stop.
to Start.
B
B
6-12
Start-Up
Start-Up
A. Dig Inputs
A. Dig Inputs
Digital Inputs
Digital Inputs
configured for
configured for
2-wire control
3-wire control
no reversing
no reversing.
Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013
Go to 6-27
B. Dig
Outputs
Go to 6-49
Output
D. Done
Go to 0-1 (7. Application
Features)
6-19
Start-Up
A. Dig Inputs
Select a Digital
Input:
<1.Digital In 1>
2.Digital In 2
3.Digital In 3
4.Digital In 4
5.Digital In 5
6.Digital In 6
7.Done
Done
Go to 6-1 (B.Dig
Outputs)
B
6-5
Start-Up
A. Dig Inputs
Is REVERSE
required from
digital inputs?
<Yes>
No
6-6
B
Start-Up
A. Dig Inputs
2 wire control
uses a contact
Yes
that acts as
both STOP (Open)
& Run (Closed).
3 wire control
uses 2 contacts;
one for START
& one for STOP.
B
6-13
Start-Up
A. Dig Inputs
More
Enter choice for
Info..
Control Method
<3 wire>
3-wire
2 wire
More info
2-wire
B
6-14
Start-Up
A. Dig Inputs
Digital In1 set
to Run Forward.
Digital In2 set
to Run Reverse.
B
6-15
Start-Up
A. Dig Inputs
Digital Inputs
configured for
2-wire control
with reversing.
Go to 6-1 (B. Dig
Outputs)
Flux Vector Start Up (Strt,Stop,I/O)
B = Basic mode
Enter/
Backup
6-20
Start-Up
A. Dig Inputs
Enter choice for
Digital In1 Sel
Digital In 1
6-21
Start-Up
A. Dig Inputs
Digital In 2
Enter choice for
Digital In2 Sel
6-22
Digital In 3
Start-Up
A. Dig Inputs
Enter choice for
Digital In3 Sel
Digital In 4
6-23
Start-Up
Digital In 5
A. Dig Inputs
Enter choice for
Digital In4 Sel
6-24
Digital In 6
Start-Up
A. Dig Inputs
Enter choice for
Digital In5 Sel
6-25
Start-Up
A. Dig Inputs
Enter choice for
Digital In6 Sel
6-7
B
6-16
B
Start-Up
A. Dig Inputs
Digital Input 3
will be set to Fwd/
Reverse.
6-17
B
Start-Up
A. Dig Inputs
Digital In1 set
to Stop.
Digital In2 set
to Start.
B
6-18
Start-Up
A. Dig Inputs
Digital Inputs
configured for
3-wire control
with reversing.