Chapter 3
Setting Up Measurements
Table 20 - Transducer specification in STD (Hz) 2000 collection specification
Name
Accelerometer
76
The table for the transducer specification in the STD (Hz) 2000 collection
specification would look like this.
Base Unit
Acceleration

Measurement Input Types

The input type is part of the transducer specification (Setup > Calibration). The
transducer is part of the collection specification (Setup > Collection). You select
the collection specification when you set up the measurement definition.
The Emonitor software and the Dynamix 2500 data collector support the
following input types.
Input Type
ICP Accel
AC Coupled
DC Coupled
Manual Entry
Follow these to specify an input type.
1. Select Setup > Calibration.
2. Choose the correct Dynamix 2500 data collector from the Collector list.
3. Assign Input types, Calibration, and appropriate Units to the transducer.
Figure 14 - Transducer Calibration dialog box
Rockwell Automation Publication 1441-UM001B-EN-P - September 2012
Input Type
Units
ICP Accel
g's
Description
Use for ICP accelerometers requiring current from a power
supply.
Use for AC voltage measurements and non-ICP accelerometers.
Use for DC voltage measurements. This includes numeric
(process) measurements taken from a DC voltage output.
Use for numeric (process) measurements where you enter the
value for the measurement with the data collector keyboard.
DC Offset
0