Signals

8.
Signals
8.1.

Signals via HART

8.2.

Status signals via output contacts (digital outputs)

Characteristics
8.2.1.

Assignment of outputs

8.2.2.

Encoding of outputs

8.3.

Analogue signals

Valve position
44
SAEx 07.2
SAEx 16.2 / SAREx 07.2
HART offers different feedback signals. Configuration is possible for both data
structure and data contents.
For details regarding feedback signals via HART interface, please refer to the Manual
(Device integration) HART.
Output contacts are used to send status signals (e.g. reaching the end positions,
selector switch position, faults...) as binary signals to the control room.
Status signals only have two states: active or inactive. Active means that the
conditions for the signal are fulfilled.
The output contacts (outputs DOUT 1
Required user level: Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Signal DOUT 1 M0109
Default values:
Signal DOUT 1 = Fault
Signal DOUT 2 = End position CLOSED
Signal DOUT 3 = End position OPEN
Signal DOUT 4 = Selector sw. REMOTE
Signal DOUT 5 = Torque fault CLOSE
Signal DOUT 6 = Torque fault OPEN
High active = output contact closed = signal active
Low active = output contact open = signal active
Required user level: Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Coding DOUT 1 M0102
Signal: E2 = 0/4
20 mA (galvanically isolated)
Designation in the wiring diagram:
ANOUT1 (position)
For further information on this topic, please refer to Manual (Operation and setting).
SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART
6) can be assigned to various signals.