Mounting Positions: Modify - AUMA SAEx 07.2 Operation Instructions Manual

Multi-turn
Hide thumbs Also See for SAEx 07.2:
Table of Contents

Advertisement

Assembly
4.5.1.

Mounting positions: modify

18
SAEx 07.2
SAEx 16.2 / SAREx 07.2
Figure 11: Mounting positions C and D
Flameproof enclosure, danger of explosion!
Risk of death or serious injury.
Before opening, ensure that there is no explosive gas and no voltage.
Handle cover and housing parts with care.
Joint surfaces must not be damaged or soiled in any way.
Do not jam cover during fitting.
Electrostatic discharge ESD!
Risk of damage to electronic components.
Earth both operators and devices.
1.
Loosen screws and remove the local controls.
2.
Check whether O-ring is in good condition, correctly insert O-ring.
3.
Turn local controls into new position and re-place.
Cable damage due to twisting or pinching!
Risk of functional failures.
Turn local controls by a maximum of 180°.
Carefully assemble local controls to avoid pinching the cables.
4.
Fasten screws evenly crosswise.
SAREx 16.2 Control unit - electromechanical