Electrical Connection; Basic Information - AUMA SAEx 07.2 Operation Instructions Manual

Multi-turn
Hide thumbs Also See for SAEx 07.2:
Table of Contents

Advertisement

SAEx 07.2
SAEx 16.2 / SAREx 07.2
ACExC 01.2 Intrusive HART
5.

Electrical connection

5.1.

Basic information

Wiring diagram/terminal
plan
Permissible networks
(supply networks)
Protection on site
Power supply for the
controls (electronics)
Safety standards
SAREx 16.2 Control unit - electromechanical
Danger due to incorrect electrical connection
Failure to observe this warning can result in death, serious injury, or property damage.
The electrical connection must be carried out exclusively by suitably qualified
personnel.
Prior to connection, observe basic information contained in this chapter.
After connection but prior to applying the voltage, observe the <Commissioning>
and <Test run> chapters.
The pertaining wiring diagram/terminal plan (both in German and English) is attached
to the device in a weather-proof bag, together with these operation instructions. It
can also be requested from AUMA (state order number, refer to name plate) or
downloaded directly from the Internet (http://www.auma.com).
The controls (actuators) are suitable for for use in TN and TT networks with directly
earthed star point and a maximum voltage of 690 V AC. Use in IT networks is
permitted while observing the respective <Protection on site> for for maiximum supply
voltages of 600 V AC.
For short-circuit protection and for disconnecting the actuator from the mains, fuses
and disconnect switches have to be provided by the customer.
The current values for respective sizing is derived from the current consumption of
the motor (refer to electrical data sheet) plus the current consumption of the controls.
Table 6: Current consumption controls
Mains voltage
Permissible variation of the mains voltage
100 to 120 V AC
208 to 240 V AC
380 to 500 V AC
515 to 690 V AC
Table 7: Maximum permissible protection
Switchgear
Reversing contactor A1
Reversing contactor A2
Reversing contactor A3
Thyristor B1
Thyristor B2
Thyristor B3
If controls are mounted separately from actuator (controls on wall bracket): Consider
length and cross section of connecting cable when defining the protection required.
Use appropriate insulation monitors when working in power installations, for example
an insulation monitor measuring the pulse code.
In case of external supply of the controls (electronics): The external power supply
must have a reinforced insulation against the mains voltage in accordance with IEC
61010-1 and may only be supplied by a circuit limited to 150 VA in accordance with
IEC 61010-1.
All externally connected devices shall comply with the relevant safety standards.
Max. current consumption
±10 %
750 mA
400 mA
250 mA
200 mA
Rated power
up to 1.5 kW
up to 7.5 kW
up to 11 kW
up to 1.5 kW
up to 3 kW
up to 5.5 kW
Electrical connection
30 %
1,200 mA
750 mA
400 mA
400 mA
Max. protection
16 A (gL/gG)
32 A (gL/gG)
63 A (gL/gG)
16 A (g/R) I²t<1,500A²s
32 A (g/R) I²t<1,500A²s
63 A (g/R) I²t<5,000A²s
19